Machine Model: CBEST
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0 < T3 < Mult*TimeStep then T3 = Mult*TimeStep
- T1, T3 and T4:
- If T1 = T3 for model, T1 and T3 will be ignored (T1=0 and T3=small value).
- Ff T1 = T4 for model, T1 and T4 will be ignored (T1=0 and T4=0).
- T2, T3 and T4
- T2 = T4 for model, T2 and T4 will be ignored (T2=0 and T4=0).
- T2 = T3 for model, T2 and T3 will be ignored (T2=0 and T3=small value).
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| Pmax | Maximum power, pu |
| OutEff | Output efficiency ( ≥ 1 ) |
| InEff | Input efficiency ( ≤1 ) |
| Iacmaxpu | IACMAX (pu) |
| Kavr | AVR gain |
| T1 | AVR time constant, sec |
| T2 | AVR time constant, sec |
| T3 | AVR time constant, sec ( >0 ) |
| T4 | AVR time constant, sec |
| Vmax | Maximum AVR speed limit, pu |
| Vmin | Minimum AVR speed limit, pu ( <0 ) |
| Droop | DROOP, pu |